1. THE IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - answers>OWNER
2. RECORDS OFALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF
YEARS. - answers>3
3. THE BUILDING OWNER SHALL ASSIGN A(N) TO COMPLY WITH REQUIREMENTS. -
answers>IMPAIRMENT COORDINATOR
4. REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN FLOOR(S) ARE
CONSIDERED PLANNED REMOVAL FROM SERVICE. - answers>1
5. SHUTDOWNS AFFECTING MORE THAN FLOOR(S) ARE CONSIDERED UNPLANNED OUT
OF SERVICE CONDITIONS. - answers>1
6. NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN
HOURS. - answers>8
7. FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT
CONDITION TO THE AND THE FIRE DEPT. - answers>OWNER OF THE BUILDING
8. IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN DAYS OR IT WILL
BE CONSIDERED AN IMPAIRMENT. - answers>30
9. WHAT DOES "OOS" STAND FOR? - answers>OUT OF SERVICE
10. OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING AT FIRE DEPT. CONNECTIONS, SYS.
CONTROL VALVES, AND FIRE COMMAND CENTER - answers>TAGS
lOMoAR cPSD|3013804
11. A SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL
VALVES. - answers>MASTER FIRE SUPPRESSION PIPING CONTRACTOR
12. SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES
BEFORE AND AFTER. - answers>DRAIN TEST RESULTS
13. GREEN TAGS INDICATE THAT . - answers>NO IMPAIRMENT WAS FOUND
14. GREEN TAGS WILL BE PLACED ON THE . - answers>MAIN CONTROL VALVE
15. SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A TAG PLACED ON
THE MAIN CONTROL VALVE. - answers>RED
16. A DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM
IS FULLY OUT OF SERVICE. - answers>WHITE
17. A DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM
IS PARTIALLY OUT OF SERVICE. - answers>BLUE
18. THE IMPAIRMENT COORDINATOR WILL NOTIFY THE CARRIER, CENTRAL STATION
AND OCCUPANTS. - answers>INSURANCE
19. PRIOR TO RETURNING A SYS.TO SERVICE, THE SHALL ENSURE THATNECESSARY
TESTS AND INSPECTIONS ARE CONDUCTED. - answers>IMPAIRMENT COORDINATOR
20. GLYCERIN NOT GREATER THAN PERCENT OR GLYCOL NOT GREATHER THAN
PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - answers>50, 40
21. THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
. - answers>MAIN CONTROL VALVE