1) Manual fire alarm boxes shall be located not more than ___ feet from the entrance to each exit.
5
10
15
20
25
Feedback
907.5.2.1
Unanswered
86% got this correct
2) Horizontal and vertical sliding and rolling fire doors shall be inspected and tested __________ to confirm proper operation and full closure.
Every 30 days
Every 90 days
Every 36 months
Every 72 months
Annually
Feedback
703.4
Unanswered
62% got this correct
3) Combustible trim, excluding handrails and guardrails, shall not exceed ___ percent of the specific wall or ceiling areas to which it is attached.
10
15
20
25
Feedback
804.1
Unanswered
86% got this correct
4) Candles and open flames are allowed to be used on or near decorative vegetation while immediately supervised.
T
F
Feedback
806.4
Unanswered
92% got this correct
5) Swinging fire doors shall close from the _________ position and latch automatically.
Partially open
Partially closed
Full open
Feedback
703.2.3
Unanswered
67% got this correct
6) Combustible material shall not be stored in ________________.
(check all that apply)
Boiler rooms (Missed)
Mechanical rooms (Missed)
Lunch break rooms
Electrical equipment rooms (Missed)
Underground rooms
Feedback
315.2.3
Unanswered
74% got this correct
7) Temporary wiring for electrical power and lighting installations is allowed for a period not to exceed ___ days.
30
60
90
180
Feedback
605.9
Unanswered
65% got this correct
8) A permit is required to install stationary storage battery systems having a liquid capacity of more than ____ gallons.
25
50
75
100
Feedback
105.7.2
Unanswered
66% got this correct
9) An operational permit is required to use a building or portion thereof as a high-piled storage area exceeding _____ square feet.
300
400
500
600
Feedback
105.6.22
Unanswered
72% got this correct
10) Covered mall buildings exceeding __________ square feet shall be provided with standby power systems that are capable of operating the emergency voice/alarm communication.
25500
40000
50000
75000
Unanswered
89% got this correct
11) Manual fire alarm boxes may be any color, approved by the fire code official, that contrasts the color of the location in which they are installed.
T
F
Feedback
907.5.2.3
Unanswered
59% got this correct
12) Outside storage of combustible materials shall not be located within ___ feet of a property line.
5
10
15
20
Feedback
315.3
Unanswered
64% got this correct
13) Classify the following based on occupancy: Funeral parlor
A-1
A-2
A-3
A-4
A-5
Feedback
Ch. 2
Unanswered
51% got this correct
14) Classify the following based on occupancy: Child care facilities that provide supervision and personal care on less than a 24 hour basis for more than 5 children 2 1/2 years of age or less.
E
I-2
B
I-4
Feedback
pg. 26
Unanswered
77% got this correct
15) Extension cords and flexible cords shall not be a substitute for ______________.
Possible correct answers:
permanent wiring
Feedback
605.5
Unanswered
56% got this correct
16) Combustible storage shall be kept a minimum of ___ feet from battery chargers.
3
5
10
15
Feedback
309.2
Unanswered
61% got this correct
17) Classify the following based on occupancy: Hotels (transient)
R-1
R-2
R-3
R-4
Feedback
pg. 26
Unanswered
60% got this correct
18) An operational permit is required for the storage and handling of combustible fibers in quantities greater than __________.
100 cubic feet
100 square feet
200 cubic feet
200 square feet
Feedback
105.6.7
Unanswered
81% got this correct
19) Commercial cooking systems for low-volume cooking operations such as places of worship, seasonal businesses and senior centers shall be inspected ________.
Every month
Every 3 months
Every 6 months
Every 12 months
Feedback
Table 609.3.3.1
Unanswered
67% got this correct
20) The maximum travel distance to a fire extinguisher in a Class A, extra (high) hazard occupancy is ___ feet.
30
50
75
100
Feedback
Table 906.3 (1)
Unanswered
83% got this correct
21) The minimum corridor width shall be not less than 44 inches.
T
F
Feedback
1018.2
Unanswered
72% got this correct
22) Artwork and teaching materials shall be limited on walls of corridors to not more than ___ percent of the wall area.
15
20
25
30
Feedback
807.4.4.2
Unanswered
56% got this correct
23) A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of ___ feet and a maximum of ___ feet from the kitchen exhaust system.
5, 10
10, 15
10, 20
15, 20
15, 25
Feedback
904.11.1
Unanswered
64% got this correct
24) An operational permit is not required to melt, cast, heat treat or grind less than 10 pounds of magnesium.
T
F
Feedback
105.6.28 read carefully
Unanswered
65% got this correct
25) Stairways shall have a minimum headroom clearance of ___ inches measured vertically from a line connecting the edge of the nosings.
78
80
82
84
Feedback
1009.2
Unanswered
76% got this correct
26) Where there is a conflict between a general requirement and a specific requirement, the __________ shall be applicable.
General requirement
Specific requirement
Most stringent
Least stringent
Unanswered
57% got this correct
27) Hand-held portable fire extinguishers having a gross weight not exceeding ___ pounds shall be installed so that their tops are not more than ___ feet above the floor.
40, 3
40, 5
40, 3.5
40, 5.5
Feedback
906.9.1
Unanswered
93% got this correct
28) Fire alarm, sprinkler and standpipe systems shall be maintained in an operable condition at all times in vacant premises.
T
F
Feedback
311.2.2
Unanswered
79% got this correct
29) The first emergency evacuation drill of each school year shall be conducted within _____ days of the beginning of classes.
10
14
21
28
Feedback
408.3.1
Unanswered
63% got this correct
30) An operational permit is required for the storage, use, or handling at NTP of _____ of compressed corrosive gas.
200 cubic feet
504 cubic feet
6000 cubic feet
Any amount
Feedback
Table 105.6.8
Unanswered
63% got this correct
31) The height of manual fire alarm boxes shall be a minimum of ___ inches and a maximum of ___ inches measured vertically, from the floor level to the activating handle or lever of the box.
36, 42
36, 48
42, 48
44, 48
Feedback
907.5.2.2
Unanswered
67% got this correct
32) The minimum required distance from a structure for open burning shall not be less than ___ feet where the pile size is ___ feet or less in diameter and ___ feet or less in height.
50, 3, 2
50, 2, 3
25, 3, 2
25, 2, 3
Feedback
307.4 ex. 2
Unanswered
56% got this correct
33) Bulk storage of tires is defined as storage of tires where the area available for storage exceeds _________ cubic feet.
5000
10000
15500
20000
Feedback
902
Unanswered
52% got this correct
34) Portable outdoor fireplaces shall not be operated within ___ feet of a structure or combustible material.
5
10
15
20
Feedback
307.4.3
Unanswered
58% got this correct
35) Permit amounts for cryogenic fluids are found in which table?
Possible correct answers:
105.6.10, table 105.6.10, Table 105.6.10
Feedback
pg. 7
Unanswered
66% got this correct
36) Vehicle impact protection guard posts shall be set with the top of the posts not less than ___ feet above the ground.
3
3.5
4
4.5
Feedback
312.2 (4)
Unanswered
67% got this correct
37) Where connected to a fuel-oil piping system, the maximum amount of fuel oil storage allowed outside above ground without additional protection shall be _____ gallons.
50
200
350
660
Feedback
603.3.1
Unanswered
80% got this correct
38) Fire apparatus access roads shall have an unobstructed width of not less than ___ feet and an unobstructed vertical clearance of not less than ___ feet ___ inches.
20, 10, 6
20, 13, 6
22, 12, 8
22, 14, 10
Feedback
503.2.1
Unanswered
72% got this correct
39) Classify the following based on occupancy: Sales room
B
A-3
M
S-2
Unanswered
56% got this correct
40) Turnstiles more than ___ inches high shall meet the requirements for revolving doors.
30
36
39
42
Feedback
1008.3.1
Unanswered
46% got this correct
41) Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved mutliplug extension cords, shall serve _________.
Possible correct answers:
only one portable appliance
Feedback
605.5.1
Unanswered
62% got this correct
42) Official records shall be retained for not less than 3 years.
T
F
Feedback
104.6
Unanswered
61% got this correct
43) High-rise buildings require emergency evacuation drills ________ and shall include ________.
Quarterly, employees
Quarterly, all occupants
Annually, employees
Annually, all occupants
Feedback
Table 405.2
Unanswered
73% got this correct
44) Classify the following based on occupancy: Fences more than 6 feet high.
F-1
F-2
U
S-2
M
Feedback
Ch. 2
Unanswered
69% got this correct
45) With regards to premises identification, address numbers shall be a minimum of ___ inches high with a minimum stroke of ___ inch(es).
3, 0.5
4, 0.5
3, 1
4, 1
Feedback
505.1
Unanswered
56% got this correct
46) An approved fire safety and evacuation plan shall be prepared and maintained for Group M buildings having an occupant load of _____ or more persons or more than _____ persons above or below the lowest level of exit discharge.
(check all that apply)
100 (Missed)
200
300
400
500 (Missed)
Feedback
404.2 (11)
Unanswered
59% got this correct
47) Dumpsters and containers with an individual capacity of 1.5 cubic yards or more shall not be stored in buildings or placed within ___ feet of combustible walls, openings, or combustible eave lines.
3
5
10
15
Feedback
304.3.3
Unanswered
61% got this correct
48) An operational permit is required to operate an air-supported temporary membrane structure or a tent having an area in excess of _____ square feet.
200
250
400
500
Feedback
105.6.43
Unanswered
68% got this correct
49) An operational permit is required to manufacture, store or handle an aggregate quantity of __________ aerosol products in excess of 500 pounds net weight.
Level 2
Level 3
Level 4
Both B and C
Both A and B
Feedback
105.6.1
Incorrect
56% got this correct
50) Hand-held portable fire extinguishers having a gross weight exceeding ___ pounds shall be installed so that their tops are not more than ___ feet above the floor.
40, 3
40, 5
40, 3.5
40, 5.5