At a minimum, how many individual resistance tests must be
performed on this conductive floor? Refer to DA PAM 385-64,
Section C-3 as required. - ANSWER- Ten tests: five electrodeto-electrode and five electrode-to-ground tests
An LPS requires three-point fall-of-potential earth resistance
testing every - ANSWER- Every 24 months
When conducting a 3-point fall-of-potential earth resistance test,
what is the maximum allowable resistance reading? -
ANSWER- 25 ohms
When conducting a bonding resistance test, what is the
maximum allowable reading? - ANSWER- 1 ohm
How many individual bonding resistance tests are required on an
integral LPS with 12 air terminals and 2 down conductors? -
ANSWER- 24
Which storm warning system measures the strength of
atmospheric electric fields and warns of the possibility of
lightning strikes? - ANSWER- Pre-strike
Which hazardous classified location division poses the least
probability of ignition or explosion? - ANSWER- Division 2
Which material belongs to hazardous classified location Class
II? - ANSWER- coal dust
Which material belongs to hazardous classified location Class I?
- ANSWER- acetylene gas
Which HERO classification describes items that may explode or
detonate if exposed to EMR? - ANSWER- HERO UNSAFE
Which of the following is NOT a hazard posed by
electromagnetic radiation? - ANSWER- WRONG ignition of
fuel and other combustibles
WRONG generation of extreme heat in the human body
For guidance on lightning protection requirements, you use AFI
32-1065 and - ANSWER- NFPA 780
You need to inspect an LPS that has vertical poles connected to
overhead cables that stretch the length of the structure. What
type of LPS does this describe? - ANSWER- catenary
How many feet radius does the DoD require for an LPS zone of
protection? - ANSWER- 100ft
While conducting an LPS inspection, you discover the scenario
illustrated in the image below. Do you write it up as a
discrepancy? - ANSWER- yes, because the air terminal is not
attached to a conductor.
While conducting an LPS inspection, you see down conductors
like those illustrated in the image below. Do you write it up as a
discrepancy? - ANSWER- yes, because mast down conductors
should be 180 degrees apart
How many inches should the tip of an air terminal be above the
object or area it protects? - ANSWER- WRONG 24
WRONG 18
A 30-foot building has a metal light fixture located 23 feet from
the ground. Which condition is used to determine if the light
fixture must be bonded to the LPS? Refer to the bonding job aid
as required. - ANSWER- condition 2a(2)